Skip to content

G3512 750kW Gas Generator Set

At a glance data:

Gas Standby Rating:
750 ekW @ 0.8pf
Fuel Type:
Natural Gas, Hydrogen Blend (up to 5%)
Emissions/Fuel Strategy:
U.S. EPA Certified for Non-Emergency Stationary Genset
RPM:
1800 rpm

Overview

Generator Set Specifications

Gas Standby Rating:
750 ekW @ 0.8pf
Fuel Type:
Natural Gas, Hydrogen Blend (up to 5%)
Emissions/Fuel Strategy:
U.S. EPA Certified for Non-Emergency Stationary Genset
RPM:
1800 rpm
Frequency:
60 Hz
Displacement:
3173in³

Engine Specifications

Engine Model:
G3512
Displacement:
3173in³
Aspiration:
TA
Bore:
6.7in
Stroke:
7.5in

Generator Set Dimensions

Length:
205.7in
Width:
90in
Height:
99.4in
Weight:
27500lb

Engine Specifications

Governor Type:
ADEM A4

Standard Equipment

air inlet

  • Dual air cleaners, 1 per side, with service indicator
  • Two-element single-stage air cleaner with enclosure and service indicator

control panel

  • Cat ECS 100

cooling

  • Engine driven pumps for jacket water and separate circuit aftercooler
  • Jacket water and SCAC engine-driven pumps
  • Jacket water and SCAC thermostats
  • LH or RG connections when radiator is not selected
  • Package mounted radiator

fuel

  • NOx sensor based air-fuel-ratio control
  • 0.5 to 5 psi engine fuel inlet pressure
  • Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
  • Gas Train: NFPA37 and CSA B149.3

exhaust

  • Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
  • Dry exhaust manifolds, insulated and shielded
  • Cat-flanged face outlet on turbocharger

fuel system

  • Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
  • Throttle plate, 24V DC actuator, controlled by GECM
  • Engine-installed electronic control valve
  • Gas pressure regulator
  • 24V DC energized-to-run (ETR) gas shutoff valve

general

  • Crankshaft vibration damper and guard
  • Operation and maintenance manuals
  • Parts book
  • Paint- Caterpillar Yellow except rails and radiators gloss black
  • RH Service

lubrication

  • Gear type lube oil pump
  • Cartridge style oil filter

generator

  • Anti-condensation space heater
  • Winding temperature detectors
  • NEMA Class H insulation
  • SR5
  • Permanent Magnet Excitiation
  • Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter

governing system

  • ADEM A4

ignition system

  • Individual Cylinder Detonation Sensitive Timing (DST)
  • Electronic Ignition System (controlled by ADEM A4)

governing

  • ADEM A4 speed governor with 4 to 20ma (0V to 5V) speed input

starting/charging

  • 24V DC starting motors
  • Batteries with rack and cables
  • Electric Starter

Optional Equipment

air inlet

  • Mounting brackets and piping
  • Air cleaner with precleaner

circuit breakers

  • S LSI, G LSIG, P LSIG-P, 4th Digit Type
  • Right, left, rear mounted
  • 1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
  • 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
  • 2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
  • 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
  • 3-pole (IEC 947-2 rated)
  • Frame mounting

control panel

  • Remote annunciator
  • Local alarm module
  • Local PC monitoring
  • Engine failure relay
  • Remote PC monitoring

cooling

  • Coolant level drain line with valves, fan with guard
  • Remote radiator for JW and SCAC circuits, level switch included but not wired
  • Inlet/Outlet connections

exhaust

  • 305 mm (12in.) elbow
  • 18, 25 dBA Attenuation
  • Flexible fittings
  • 305 mm (12 in.) muffler
  • 305mm (12 in) spark arresting muffler
  • 305 mm (12 in.) flange

fuel system

  • 3, 0-100 kPag, 4-20mA gas train pressure sensors

general

  • Special paint order
  • US AID emblem
  • Tool set
  • Digital diagnostic tool

generator

  • Cable access box
  • Generator air filter
  • European bus bars
  • Low voltage extension box
  • Bearing temperature detectors

starting/charging

  • 20A, 24VDC battery charger
  • Battery with cables and rack
  • Jacket water heater
  • 45A, 24V charging alternator (requires engine driven pumps)

grid code compliance

  • 60 Hz: USA