Skip to content

C1.1 Generator Set

At a glance data:

Maximum Rating:
8.8 ekW
Minimum Rating:
8.0 ekW
Emissions/Fuel Strategy:
R96/EUIIIa Equivalent
Voltage:
110 to 480 Volts

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications

Maximum Rating:
8.8 ekW
Minimum Rating:
8.0 ekW
Emissions/Fuel Strategy:
R96/EUIIIa Equivalent
Voltage:
110 to 480 Volts
Frequency:
60 Hz
Speed:
1800 rpm
Duty Cycle:
Standby, Prime

Engine Specifications

Engine Model:
C1.1, In-line 4, 4-cycle diesel
Bore:
3in
Stroke:
3.2in
Displacement:
69in³
Compression Ratio:
23.0:1
Aspiration:
Naturally Aspirated
Fuel System:
Indirect Injection
Governor Type:
Mechanical

Generator Set Dimensions

Length - Maximum:
55.1in
Width - Maximum:
24.4in
Height - Maximum:
39.2in

Standard Equipment

air inlet system

  • Air cleaner; light duty with disposable element

control panel

  • GCCP 1.3

cooling system

  • Coolant drain line with valve
  • Caterpillar extended life coolant
  • Radiator and cooling fan with guards
  • Fan drive, battery charging alternator drive

exhaust system

  • Stub pipe, gaskets, raincap & SAE exhaust flange for customer use - shipped loose

fuel system

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied

generators and generator attachments

  • 12 Leads
  • IP23 Protection
  • Segregated low voltage (AC/DC) wiring panel
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • Voltage regulator (single phase sensing)
  • Tower panel, IP22, bottom cable entry

governing system

  • Mechanical governing system

lube system

  • Lubricating oil
  • Oil drain line with valve

mounting system

  • Includes lifting provisions and termination points for coolant
  • Captive linear vibration isolators between base and engine-generator

starting / charging system

  • 12 Volt battery with rack and cables

general

  • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

alternator options

  • Coastal insulation protection

certificates

  • European upgrade to STD set for CE certificate
  • Global certification for CIS

circuit breakers

  • Padlockable breaker device
  • 4 Pole Circuit breaker

control panel

  • Battery charger
  • Volt free contacts for common alarm
  • Volt free contacts for genset running
  • Emergency stop with key
  • GCCP 1.3

cooling system

  • Coolant heater

enclosures

  • Single point lift for enclosure
  • Sound attenuated enclosure (GALV)

fuel system

  • Fuel transfer control
  • Base feet
  • 1000 hr extended service interval
  • Skidbase for enclosures
  • Skidbase for open sets
  • DEFRA bunded fuel tank
  • Low fuel level alarm

mounting options

  • Industrial silencer removal
  • Battery removal
  • Silencer installation kit

special test and inspection

  • PGS Test report @ 1.0 power factor

general

  • Radiator stone guard
  • Packing case - canopied set
  • Packing case - compact set
Enclosure

6.8-22 kVA SA Enclosure

Maximum Rating:
8.8 ekW
Minimum Rating:
8.0 ekW
Emissions/Fuel Strategy:
R96/EUIIIa Equivalent
Voltage:
110 to 480 Volts