Skip to content

DE165 GC Generator Set (60 Hz)

At a glance data:

Maximum Rating:
150 ekW
Minimum Rating:
150 ekW
Emissions/Fuel Strategy:
Non Regulated
Voltage:
220 to 480 Volts

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications

Maximum Rating:
150 ekW
Minimum Rating:
150 ekW
Emissions/Fuel Strategy:
Non Regulated
Voltage:
220 to 480 Volts
Frequency:
60 Hz
Speed:
1800 rpm
Duty Cycle:
Standby

Engine Specifications

Engine Model:
C7.1 I-6, 4-Cycle Diesel
Bore:
4.1in
Stroke:
5.3in
Displacement:
427.8in³
Compression Ratio:
16.0:1
Aspiration:
Turbocharged Air To Air Charge Cooled
Fuel System:
Inline
Governor Type:
Mechanical

Generator Set Dimensions

Length - Maximum:
130.9in
Width - Maximum:
44.6in
Height - Maximum:
65.6in
Dry Weight - Genset (maximum):
4043lb

Standard Equipment

engine

  • C7.1, Inline 6 cylinder, 4 stroke diesel

control panels

  • GCCP 1.1

governor

  • Mechanical governor

enclosure

  • Cat GC enclosure

alternator

  • A Frame standard alternator

fuel storage

  • Single wall 8 hour fuel tank

air, cooling & exhaust

  • Enclosure silencer

general

  • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

auxiliary supply voltage

  • 120V

certification

  • Australia, CIS, Gulf Certification
  • Certificate of Conformance

alternator requirements

  • Space heater

fuel storage

  • Dual wall 8 hour fuel tank
  • Single wall tank with containment
  • Low fuel level alarm
  • High fuel level alarm
  • Low fuel level shutdown

genset control

  • Battery charger
  • Volt free contacts for common alarm
  • Panel mounted audible alarm
  • Volt free contacts for genset running
  • Earth leakage
  • USB to RS485 Communications device
  • Earth fault
  • Emergency stop with key
  • Coolant heater
  • Battery
  • Low coolant level shutdown
  • Standby Pack (Smart Jacket water heater, Battery charger)

fuel systems

  • High fuel level alarm

circuit breaker

  • 3 Pole Circuit breaker 630A
  • 4 Pole Circuit breaker 250A
  • 4 Pole Circuit breaker 200A
  • 3 Pole Circuit breaker 200A
  • 4 Pole Circuit breaker 630A
  • 4 Pole Circuit breaker 400A
  • Circuit breaker padlock
  • Neutral earth link
  • Overload via alarm switch on breaker
  • 3 Pole Circuit breaker 400A

testing & packaging

  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8PF