Skip to content

3412C | 750kVA 50Hz Generator Set

At a glance data:

Maximum Rating:
680 kVA
Minimum Rating:
680 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 415 Volts

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications

Maximum Rating:
680 kVA
Minimum Rating:
680 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 415 Volts
Frequency:
50 Hz
Speed:
1500 rpm
Duty Cycle:
Standby, Prime

Engine Specifications

Engine Model:
3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore:
5.4in
Stroke:
6in
Displacement:
1648.86in³
Compression Ratio:
13:01
Aspiration:
Turbocharged, Air to Air Aftercooled
Fuel System:
Pump and Lines
Governor Type:
ADEM™ A5

Generator Set Dimensions

Length - Maximum:
162.4in
Width - Minimum:
75in
Width - Maximum:
78.3in
Height - Maximum:
75in
Dry Weight - Genset (minimum):
12039lb
Dry Weight - Genset (maximum):
13030lb

Standard Equipment

air inlet system

  • Air cleaner, single element canister type with service indicator

control panel

  • GCCP Control panel
  • Over/under voltage (27 / 59)
  • Environmental sealed front face
  • Generator phase sequence
  • Communications
  • Digital I/O module
  • Features include:
  • 2 Programmable relay outputs (Form C)
  • Compatible with the following optional modules:
  • Customer data link (Modbus RTU)
  • 4 programmable relay outputs (Form A)
  • Amps (per phase & average)
  • kVA (per phase, average & percent)
  • Text alarm/event descriptions
  • Low coolant level
  • Generator temperature monitoring module
  • Run/auto/ stop/control
  • Overspeed
  • Serial annunciator module data link
  • Emergency stop pushbutton
  • Frequency (Hz)
  • RPM
  • 6 programmable digital inputs
  • Oil pressure (psi, kPa or bar)
  • Engine cycle crank
  • Operating hours
  • Local annunciator
  • coolant temperature
  • kW-hr (total)
  • Programmable protective relaying functions:
  • kW (per phase, average & percent)
  • Low oil pressure
  • Reverse power (kW) (32)
  • Remote Serial annunciator
  • DC volts
  • Power factor (per phase & average)
  • Remote CAN annunciator
  • 24 Volt DC operation
  • Accessory module data link
  • Failure to start (overcrank)
  • Over/under frequency (81 o/u)
  • kVAr (per phase, average & percent)
  • Warning/shutdown with common LED indication of shutdowns for:
  • Low coolant temperature
  • 2 Programmable digital outputs
  • Reverse reactive power (kVAr) (32RV)
  • Emergency stop
  • Digital indication for:
  • High coolant temperature
  • Speed adjust
  • Voltage adjust
  • Volts (L-L & L-N)
  • Overcurrent (50 / 51)

cooling system

  • Fan and belt guards
  • Coolant drain line with valve, piped to edge of base
  • Caterpillar extended life coolant
  • Coolant level shutdown
  • Radiator with guard (Sized for 50 degrees C)

exhaust system

  • Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose

fuel system

  • Flexible fuel lines terminated on base
  • Fuel priming pump
  • Primary and Secondary fuel filters
  • Water seperator

generator and attachments

  • 3-phase sensing
  • SR4B self excited
  • Class H insulation
  • 2:1 Volts/Hz
  • Reactive droop
  • VR6 voltage regulator
  • Busbar termination
  • Class F temperature rise
  • 12 Leads

governing system

  • Cat electronic governor

lube system

  • Oil drain line with valve, piped to edge of base
  • Lubricating oil
  • Oil filter
  • Fumes disposal, piped to front of radiator

mounting system

  • Base, formed steel with linear vibration isolators between base and engine-generator

starting / charging system

  • Battery with rack, cables
  • 45 amp Charging alternator
  • 24 volt starting motor
  • Fuel shutoff solenoid

Optional Equipment

air inlet system

  • Open element air cleaners
  • Heavy duty air cleaners
  • Dual element air cleaners

circuit breakers

  • 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
  • 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip

control panel

  • First local annunicators
  • Local discrete I/O package
  • Generator temperature monitoring package
  • Ground fault relay
  • Remote custom annunicator
  • GCCP Control panel
  • Generator running VFC
  • GCCP Control panel
  • Vandal proof panel door
  • Common alarm/shutdown relay

cooling system

  • Jacket water heaters
  • Radiator duct flange

european certifications

  • Eurasian Conformity (EAC) mark

exhaust system

  • Elbow kit
  • Manifold and turbocharger guards
  • Through wall installation kit
  • Mufflers

generator and attachments

  • Digital voltage regulator
  • Oversize and premium generators
  • Space heater
  • Permanent magnet excitation (PMG)

lube system

  • Manual sump pump

mounting system

  • Fuel tank base (1200 ltr)

special tests / reports

  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8 power factor

starting / charging

  • Heavy duty starting system
  • Battery chargers
  • Battery disconnect switch
  • Oversize batteries

governing system

  • Electronic load share