3516E Low Voltage Generator Set
- new - Products
- 3516E Low Voltage Generator Set
At a glance data:
Standby Rating:
2750 ekW
Prime Power Rating:
2500 ekW
Emissions/Fuel Strategy:
Tier 2, Low NOx
Voltage:
416 to 13,800 Volts
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
Standby Rating:
2750 ekW
Prime Power Rating:
2500 ekW
Emissions/Fuel Strategy:
Tier 2, Low NOx
Voltage:
416 to 13,800 Volts
Frequency:
60 Hz
Speed:
1800 rpm
Duty Cycle:
Standby, Mission Critical, Prime
Maximum Rating:
2750 ekW
Minimum Rating:
2500 ekW
Engine Specifications
Engine Model:
3516E, V-16, 4-Stroke, Water-Cooled Diesel
Bore:
6.69in
Stroke:
8.47in
Displacement:
4765in³
Compression Ratio:
14.7:1
Aspiration:
ATAAC
Fuel System:
EUI
Governor Type:
Adem™ A5
Generator Set Dimensions
Length - Maximum:
303.3in
Width - Maximum:
104.0in
Height - Maximum:
131.6in
Dry Weight - Genset (maximum):
40750lb
Standard Equipment
air inlet system
- Single element canister type with service indicator
- Air cleaner
cooling
- Package mounted radiator
exhaust
- Exhaust flange outlet
fuel
- Primary fuel filter with integral water separator
- Fuel priming pump
generator
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
power termination
- Busbar
starting/charging
- Heavy duty starting system
- Charging alternator
control panel
- Communications:
- 6 Programmable digital inputs
- Programmable protective relaying functions:
- Low oil pressure
- Environmental sealed front face
- Volts (L-L & L-N)
- Emergency stop pushbutton
- Serial annunciator module data link
- Reverse power (kW) (32)
- Engine cycle crank
- Lamp test
- Over/under frequency (81 o/u)
- kW-hr (total)
- Speed adjust
- True RMS AC metering, 3-phase, +/-2% accuracy
- Engine cool-down timer
- Overcurrent (50/51)
- Reverse reactive power (kVAr) (32RV)
- kW (per phase, average & percent)
- kVAr-hr (total)
- Generator phase sequence
- Oil pressure (psi, kPa or bar)
- Low coolant temperature
- Amps (per phase & average)
- Generator mounted - rear facing
- Over/under voltage (27/59)
- Low coolant level
- Accessory module data link
- kVAr (per phase, average & percent)
- Cat ECS controller includes:
- Failure to start (overcrank)
- 2 Programmable relay outputs (Form C)
- Cat ECS 100
- Overspeed
- 2 Programmable digital outputs
- DC volts
- Frequency (Hz)
- High coolant temperature
- Warning/shutdown with common LED indication of shutdowns for:
- Operating hours
- 4 Programmable relay outputs (Form A)
- Coolant temperature
- Power factor (per phase & average)
- Digital indication for:
- Panel lights
- Text alarm/event descriptions
- Controls:
- 24 Volt DC operation
- Alarm acknowledge
- Customer data link (Modbus RTU)
- kVA (per phase, average & percent)
cooling system
- Caterpillar extended life coolant
- Coolant drain line with valve
- Coolant level sensors
- JWAC
- Radiator fan and fan drive
- Fan and belt guards
exhaust system
- Dry exhaust manifold
- Flanged faced outlet(s)
fuel system
- Secondary fuel filters
- Flexible fuel lines - shipped loose
- Fuel cooler; not included with packages without radiator
- Fuel priming pump
generators and attachments
- Form wound
- 3 Phase brushless, Salient pole
- Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
- Winding temperature detectors
- Permanent magnet excitation (PMG)
- Anti-condensation space heater
- Right side extension terminal box, busbar connections, top mounted, bottom cable entry
- 6 Lead
- NEMA standard hole pattern
governing system
- ADEM III
literature
- Parts book
- Operation & Maintenance Manual
lube system
- Integral lube Oil cooler
- Fumes disposal
- Oil drain lines and valve
- Oil filter, filler and dipstick
- Lubricating oil
- Gear type lube oil pump
mounting system
- Rubber anti-vibration mounts - shipped loose
- Rails - engine/generator/radiator mounting
starting / charging system
- Battery disconnect switch
- 45 Amp Charging alternator
- Battery and battery rack w/cables
- 24 Volt electric starting motor
general
- Flywheel and flywheel housing-SAE No. 00
- SAE standard rotation
- Paint - Caterpillar yellow with high gloss black rails & radiator
- Right hand servicing
Optional Equipment
air inlet system
- Air inlet protection
- Remote air inlet adapters
- Dual element air cleaners
- Heavy duty air cleaners
circuit breakers
- Busbar connections
- P Frame breaker connections
- R Frame breaker connections
- Optional busbar power connections
- Circuit breaker harnesses
- Masterpact breaker connections
- Cable entry options
- 2000, 2500, 3200, 4000 Amp, 4 Pole, IEC rated Circuit breakers
- 2000, 2500, 3200, 4000, 5000 Amp, 3 Pole, IEC rated Circuit breakers
- 1600, 2000, 2500, 3000, 4000, 5000 Amp, 3 Pole, UL-100% rated Circuit breakers
power termination
- Circuit breakers, IEC compliant
control panel
- Customer interface options
- Mounting group - External box clips
- EMCP 4.4
- PC monitoring (Remote and local)
- Ground
- Load share module options
- Annunciator modules
- Auxiliary box
- Language options
- Remote speed adjust
- Vandal proof panel door
- Voltage raise/lower switch
- Generator temperature monitoring
cooling system
- Expansion tanks
- Optional Serpentine radiators
- Water level switch gauges
- Optional ATAAC radiators
exhaust system
- Flexible fittings
- Elbows
- Flanges and exhaust fittings
- Flanges
- Y Adapters
- Mufflers
fuel system
- Duplex fuel filters
- Primary fuel filters
generators and attachments
- Differential current transformers - 8.7 and 15 kV class
- Alternator air cleaners
instrumentation
- Pyrometer and thermocouples
lube system
- Manual prelube pump
- Lube oil in standard sump
- Oil level regulator
- Electric prelube pumps
mounting system
- Spring type vibration isolators
- IBC Seismic vibration isolators NORAD
- Puck style low efficiency lsolators
power connections
- Neutral ground connections
- 2700 & 3000 Frame
- Grounding groups
special tests / reports
- IBC Certifications
- Generator set test report
- Torsional vibration analysis
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
- Standard engine test charge
- Fuel consumption test
- Generator set consumption test
starting / charging system
- Starter cover
- Electric starting motors
- Air pressure regulator
- 24 Volt battery set - Dry
- Jacket water heaters
- Engine barring group
- 10, 20, 35 and 50 Amp Battery chargers
- Air starting motors
general
- Special paint colors
- US aid emblem
Similar Products
DE75AE0 (50 Hz) Generator Set
Standby Rating:
2750 ekW
Prime Power Rating:
2500 ekW
Emissions/Fuel Strategy:
Tier 2, Low NOx
Voltage:
416 to 13,800 Volts
C9 Generator Set
Standby Rating:
2750 ekW
Prime Power Rating:
2500 ekW
Emissions/Fuel Strategy:
Tier 2, Low NOx
Voltage:
416 to 13,800 Volts
DE165E0 (50 Hz) Generator Set
Standby Rating:
2750 ekW
Prime Power Rating:
2500 ekW
Emissions/Fuel Strategy:
Tier 2, Low NOx
Voltage:
416 to 13,800 Volts