C27 ACERT Tier 4i Oilfield Diesel Generator Set

At a glance data:

Maximum Rating:
725 ekW (907 - 1035 kVA)
Minimum Rating:
725 ekW (907 - 1035 kVA)
Emissions/Fuel Strategy:
U.S. EPA Tier 2, U.S. EPA Tier 4 interim
Aspiration:
Turbocharged, aftercooled

Overview

Producing oil and gas is a complex task that requires equipped designed specifically for the oilfield. Cat C-Series oilfield diesel generator sets offer a rugged design capable of withstanding harsh conditions in the oilfield. Decades of experience in engine manufacturing combined with the latest electronics deliver the highest performance, safe operation, low emissions, and simplified operator interface. Cat generator sets are backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty. C27 ACERT oilfield diesel generator set. Ratings: 725 ekW (1035 kVA) @ 60 Hz (1800 rpm) meets U.S. EPA Tier 4 interim emission standards.

Engine Specifications

Maximum Rating:
725 ekW (907 - 1035 kVA)
Minimum Rating:
725 ekW (907 - 1035 kVA)
Emissions/Fuel Strategy:
U.S. EPA Tier 2, U.S. EPA Tier 4 interim
Aspiration:
Turbocharged, aftercooled
Manifold Type:
Dry
Bore:
5.4in
Stroke:
6.0in
Displacement:
1648.0in³
Engine Control and Protection:
ADEM A4
Generator Set Control:
EMCP 4.2
Generator:
SR4B
Fuel System:
MEUI
Frequency - Speed:
60 Hz (1800 rpm)

Capacity for Liquids

Fuel:
Diesel

Dimensions

Length:
186.0in
Width:
77.0in
Height:
86.0in
Weight:
20000.0lb

Standard Equipment

air inlet system

  • Heavy-duty dual element air cleaner
  • Service indicator

cooling system

  • Radiator package mounted (50° C)
  • Side-by-side cores
  • Coolant drain line with valve at edge of base
  • Coolant level sight gauge
  • Fan and belt guards
  • Cat Extended Life Coolant
  • Metal top and bottom tanks

exhaust system

  • Dry exhaust manifold

fuel system

  • Primary fuel filter
  • Secondary fuel filter
  • Fuel priming pump
  • Fuel transfer pump

generator

  • SR4B
  • Class H insulation
  • Random wound
  • IP23 protection
  • Cat DVR
  • Permanent magnet excitation
  • Two-bearing, close coupled alignment

controls

  • ADEM A4 ECU
  • EMCP 4.2 control panel
  • Emergency stop pushbutton

lube system

  • Oil cooler
  • High efficiency oil filter
  • Oil drain valves
  • Fumes disposal
  • Gear-type lube oil pump

mounting system

  • Heavy-duty oilfield welded steel base (skiddable)
  • Anti-vibration mounts
  • Designed welded base for increased durability (C-channel design)

starting/charging system

  • 24-volt starting motor
  • 45-amp charging alternator

general

  • Paint — Caterpillar yellow except rails and radiators (gloss black)
  • Flywheel and flywheel housing — SAE No. 0
  • Engine lifting eyes

Optional Equipment

air inlet system

  • Pre-cleaners

control system

  • Direct rack control

cooling system

  • Jacket water heater

exhaust system

  • Manifold and turbocharger guards
  • Expander

generator

  • Self excited

starting/charging system

  • Air starting motor

mounting system

  • Short base - 4725 mm (186 in) total length (does not include drag bars)