3512C Generator Set
- new - Products
- 3512C Generator Set
At a glance data:
Standby Rating:
1750 ekW
Prime Power Rating:
1600 ekW
Emissions/Fuel Strategy:
U.S. EPA Cert., Tier 2
Voltage:
380 to 13800 Volts
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
Standby Rating:
1750 ekW
Prime Power Rating:
1600 ekW
Emissions/Fuel Strategy:
U.S. EPA Cert., Tier 2
Voltage:
380 to 13800 Volts
Frequency:
60 Hz
Speed:
1800 rpm
Duty Cycle:
Standby, Mission Critical
Maximum Rating:
1750 ekW
Minimum Rating:
1600 ekW
Engine Specifications
Engine Model:
3512C ATAAC, V-12, 4-Stroke Water-Cooled Diesel
Bore:
6.69in
Stroke:
8.46in
Displacement:
3574in³
Compression Ratio:
14.7:1
Aspiration:
TA
Fuel System:
Electronic unit injection
Governor Type:
ADEM™ A3
Generator Set Dimensions
Length - Maximum:
262.9in
Width - Maximum:
89.8in
Height - Maximum:
110in
Dry Weight - Genset (maximum):
32660lb
Standard Equipment
air inlet system
- Air cleaner; single element canister type with service indicator
cooling
- Package mounted radiator
exhaust
- Exhaust flange outlet
fuel
- Primary fuel filter with integral water separator
- Fuel priming pump
- Secondary fuel filters
generator
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
power termination
- Busbar
control panel
- Cat ECS Genset controller
control system
- Generator set packages include Caterpillar's voltage regulator (IVR). IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min/max exciter. Limiter and exciter diode monitor
- Emergency stop pushbutton
- Oil pressure (psi, kPa or bar)
- 1 Programmable digital outputs
- Accessory module data link
- 4 Programmable relay outputs (Form A)
- kVAr-hr (total)
- Reverse power (kW) (32)
- kVAr (per phase, average & percent)
- Amps (per phase & average)
- Over/under frequency (81 o/u)
- Cat ECS 100
- PLC functionality
- 1 Programmable relay outputs (Form C)
- Programmable protective relaying functions:
- RPM
- Frequency (Hz)
- Low coolant level
- Number of I/O varies on options selected
- Lamp test
- kVA (per phase, average & percent)
- Emergency stop
- kW (per phase, average & percent)
- Engine cool-down timer
- Speed adjust
- Generator phase sequence
- Over/under voltage (27/59)
- Warning/shutdown with common LED indication of shutdowns for:
- Customer data link (Modbus RTU)
- Volts (L-L & L-N)
- High coolant temperature
- Engine cycle crank
- True RMS AC metering, 3-phase, +/-2% accuracy
- Low coolant temperature
- Low oil pressure
- Cat connect
- Digital indication for:
- Communications
- Environmental sealed front face
- Reverse reactive power (kVAr) (32RV)
- 24 Volt DC operation
- Power factor (per phase & average)
- Overspeed
- Auto/start/stop control
- Load histogram feature
- Controls:
- Failure to start (overcrank)
- Customizable screens
- kW-hr (total)
- Text alarm/event descriptions
- Alarm acknowledge
- Overcurrent (50/51)
- Generator mounted - rear facing
- Coolant temperature
- DC volts
governing system
- ADEM III
cooling system
- SCAC
- Fan and belt guards
- Caterpillar extended life coolant (Not included with packages without radiator, installed SF44CTS
- Coolant level sensors (Not included with packages without radiator)
- Radiator fan and fan drive
- Coolant drain line with valve
exhaust system
- Flanged faced outlet(s)
- Dry exhaust manifold
fuel system
- Secondary fuel filters
- Fuel priming pump
- Fuel cooler; not included with packages without radiator
- Flexible fuel lines - shipped loose
generators and attachments
- Random wound
- Permanent magnet excitation (PMG)
- High voltage
- Six lead
- NEMA standard hole pattern
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
- Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
- NEMA standard hole pattern
- Winding temperature detectors
- NEMA standard hole pattern
- Internal excitation (IE)
- Form wound
- 3 Phase brushless, Salient pole
- Busbar connections, right side extension box, bottom cable entry
- Low voltage:
- Busbar connections, top center mounted, top cable entry
- Medium voltage:
literature
- Parts book
lube system
- Oil drain lines and valve
- Lubricating oil
- Oil filter, filler and dipstick
- Fumes disposal
- Gear type lube oil pump
- Integral lube Oil cooler
mounting system
- Rubber anti-vibration mounts - shipped loose
starting / charging system
- Battery and battery rack w/cables
- 45 Amp Charging alternator
- 24 Volt electric starting motor
- Battery disconnect switch
general
- Paint - Caterpillar yellow except rails and radiators gloss black
- SAE standard rotation
- Right hand servicing
- Flywheel and Flywheel housing-SAE No. 00
- Paint - Caterpillar yellow with high gloss black rails & radiator
Optional Equipment
control panels
- Digital I/O module
- EMCP 4.4
- Load share module
- Remote monitoring software
- Generator temperature monitoring & protection
exhaust
- Exhaust mufflers
air inlet system
- Heavy duty air cleaner
- Single element filter
generator
- Permanent magnet excitation (PMG)
- Anti-condensation heater
- Internal excitation (IE)
- Oversize and premium generators
power termination
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
cooling system
- Standard installed radiators
- Standard installed ATAAC radiators
- Optional installed ATAAC radiators
- Water level switch gauges
- Coolant
- Optional installed radiators
exhaust system
- Flanges
- Flange and exhaust expanders
- Flexible fittings
- Elbows
- Y Adapters
- Mufflers
fuel system
- Primary fuel filter
starting/charging
- Heavy duty starting system
- Charging alternator
- Battery chargers
- Oversize batteries
- Air starting motor with control and silencer
- Jacket water heater
generators and attachments
- 1400, 1600, 2700 Frames
- Space heater
- Generator conversion from IE to PM
- Differential current transformers (DCT) 15 kV class
- RW, IE, 6 Leads, Pitch 0.6667
- Generator air cleaner
- Low voltage: 380,440 / 480 Volts, 3 Phase, 1800 rpm
- Differential current transformers (DCT) 8.7 kV class
instrumentation
- Wiring GP W/O cyl sensors
- Pyrometer and thermocouples
lube system
- Oil drains
- Lubrication oil in standard sump
- Oil level regulator
- Prelube pumps
general
- US aid emblem
- The following options are based on regional and product configuration:
- Automatic transfer switches (ATS)
- EU Certificate of Conformance (CE)
- CSA Certification
- Integral & sub-base UL listed dual wall fuel tanks
- EEC Declaration of Conformity
- UL 2200 package
- Integral & sub-base fuel tanks
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- Enclosures: Sound attenuated, weather protective
crankcase protection
- Crankcase ventilation system
- No explosion relief valves
- No crankcase explosion relief valves
- Explosion relief valves
mounting system
- Spring type vibration isolators
- IBC vibration isolators
- Puck style low efficiency isolators
mounting
- IBC isolators
- Rubber anti-vibration mounts
- Spring type vibration isolators
power connections
- 1600 ,2000, 2500, 3000, 4000 Amp, 3 Pole, UL-100% rated Circuit breakers
- Grounding groups
- Neutral ground connections
- Right side power connections
- Rear power connections
- Left side power connections
- Six lead, six terminal option
- 2000, 2500, 3200 Amp, 3 Pole, IEC rated Circuit breakers
- Center post busbars
- 2000, 2500 Amp, 4 Pole, IEC rated Circuit breakers
- Cable entry - right side
special tests / reports
- Fuel consumption test
- Generator test report
- IBC seismic Certification
- PGS Test report @ 1.0 power factor
- Standard engine test charge
- CSA Certification
- Generator fuel consumption test
- Torsional vibration analysis
- PGS Test report @ 0.8 power factor
starting / charging system
- 24 Volt battery set - Dry
- Air pressure regulator
- 10 Amp Battery charger
- Air starting motor
- 35 Amp Battery charger
- Jacket water heaters
- Starter cover
- Engine barring device
- Batteries, racks and cables:
- Electric starting motors
Cat Switchgear
Standby Rating:
1750 ekW
Prime Power Rating:
1600 ekW
Emissions/Fuel Strategy:
U.S. EPA Cert., Tier 2
Voltage:
380 to 13800 Volts
Similar Products
DE75AE0 (50 Hz) Generator Set
Standby Rating:
1750 ekW
Prime Power Rating:
1600 ekW
Emissions/Fuel Strategy:
U.S. EPA Cert., Tier 2
Voltage:
380 to 13800 Volts
C9 Generator Set
Standby Rating:
1750 ekW
Prime Power Rating:
1600 ekW
Emissions/Fuel Strategy:
U.S. EPA Cert., Tier 2
Voltage:
380 to 13800 Volts
DE165E0 (50 Hz) Generator Set
Standby Rating:
1750 ekW
Prime Power Rating:
1600 ekW
Emissions/Fuel Strategy:
U.S. EPA Cert., Tier 2
Voltage:
380 to 13800 Volts