Skip to content

3512B Diesel Generator Set

At a glance data:

Standby Rating:
1500/1400 kW
Prime Power Rating:
1360/1275 kW
Emissions/Fuel Strategy:
Low Fuel, Low Emissions
Voltage:
380 to 480 Volts

Overview

1230 - 1500 kW at 60Hz Diesel Genset
Our industrial diesel generators produce reliable power from 1230 to 1500 kW at 60 Hz. The 3512B diesel gensets are made to provide continuous power solutions for your business operation as well as supply standby and emergency power. Diesel engines are parallelable and meet prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100%rated load in one step. Generator sets offer efficiently lower fuel consumption and emissions.
Q. Can we burn HVO (hydrotreated vegetable oil) in this generator to help achieve our Sustainability goals?
A. Yes, the 3512B can burn HVO to help reduce emissions.

Generator Set Specifications

Standby Rating:
1500/1400 kW
Prime Power Rating:
1360/1275 kW
Emissions/Fuel Strategy:
Low Fuel, Low Emissions
Voltage:
380 to 480 Volts
Frequency:
60 Hz
Speed:
1800 rpm
Duty Cycle:
Standby, Mission Critical, Prime, Continuous
Maximum Rating:
1500 kW
Minimum Rating:
1230 kW

Engine Specifications

Engine Model:
3512B TA, V-12, 4-Stroke Water-Cooled Diesel
Bore:
6.69in
Stroke:
7.48in
Displacement:
51.8in³
Compression Ratio:
14.0:1 Std 15.5:1 HD
Aspiration:
TA
Fuel System:
Electronic Unit Injection
Governor Type:
ADEM™ A3

Generator Set Dimensions

Length - Maximum:
207.8in
Width - Maximum:
90in
Height - Maximum:
94.9in
Dry Weight - Genset (minimum):
24297lb
Dry Weight - Genset (maximum):
24959lb

Standard Equipment

air inlet system

  • Air cleaner; single element canister type with service indicator

control system

  • True RMS AC metering, 3-phase, +/-2% accuracy

control panel

  • DC volts
  • 24 Volt DC operation
  • kVA (per phase, average & percent)
  • Engine cool-down timer
  • Coolant temperature
  • kW-hr (total)
  • Amps (per phase & average)
  • Over/under frequency (81 o/u)
  • Text alarm/event descriptions
  • Accessory module data link
  • Alarm acknowledge
  • Warning/shutdown with common LED indication of shutdowns for:
  • Auto/start/stop control
  • Controls:
  • Failure to start (overcrank)
  • Generator mounted - rear facing
  • kVAr (per phase, average & percent)
  • kVAr-hr (total)
  • Reverse reactive power (kVAr) (32RV)
  • Volts (L-L & L-N)
  • Serial annunciator module data link
  • 4 programmable relay outputs (Form A)
  • Lamp test
  • Operating hours
  • Overcurrent (50/51)
  • kW (per phase, average & percent)
  • Communications:
  • 6 programmable digital inputs
  • RPM
  • Engine cycle crank
  • 2 Programmable relay outputs (Form C)
  • IVR includes reactive droop capability, 3-phase voltage sensing
  • High coolant temperature
  • Digital indication for:
  • Environmental sealed front face
  • Power factor (per phase & average)
  • Speed adjust
  • Emergency stop pushbutton
  • Limiter and exciter diode monitor
  • Low oil pressure
  • EMCP 4.2B
  • Low coolant level
  • 2 Programmable digital outputs
  • KVAR/PF modes, RFI suppression, min/max exciter
  • Oil pressure (psi, kPa or bar)
  • Customer data link (Modbus RTU)
  • True RMS AC metering, 3-phase, +/-2% accuracy
  • Overspeed
  • Frequency (Hz)
  • Emergency stop
  • Generator set packages include Caterpillar's voltage regulator (IVR)
  • Reverse power (kW) (32)
  • Low coolant temperature
  • Generator phase sequence
  • Programmable protective relaying functions:
  • Over/under voltage (27/59)

cooling system

  • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
  • Fan and belt guards
  • JWAC
  • Coolant drain line with valve
  • Coolant level sensors (Not included with packages without radiator)

exhaust

  • Dry exhaust manifold
  • Flanged faced outlet(s)

fuel system

  • Fuel cooler; not included with packages without radiator
  • Fuel priming pump
  • Secondary fuel filters
  • Flexible fuel lines - shipped loose

generators and attachments

  • NEMA Class H insulation
  • Winding temperature detectors
  • Internal excitation (IE) or Permanent magnet excitation (PMG)
  • LV
  • 6 Lead
  • 60 Hz models: NEMA standard hole pattern
  • Class H temperature rise at 40C ambient (125C prime / 150C standby)
  • 3 Phase brushless, Salient pole
  • Busbar connections, top center mounted, top cable entry
  • Random wound

governing system

  • Woodward 2301A isochronous governor

lube system

  • Oil drain lines and valve
  • Lubricating oil
  • Integral lube Oil cooler
  • Fumes disposal
  • Gear type lube oil pump
  • Oil filter, filler and dipstick

mounting system

  • Rails - engine/generator/radiator mounting
  • Rubber anti-vibration mounts - shipped loose

starting / charging system

  • Battery disconnect switch
  • Battery and battery rack w/cables
  • 24-Volt electric starting motor
  • 50 Amp Charging alternator

general

  • SAE standard rotation
  • Paint - Caterpillar yellow with high gloss black rails & radiator
  • Flywheel and Flywheel housing-SAE No. 00
  • RH service

Optional Equipment

air inlet system

  • Air cleaner: Includes installed single element Cat filter and service indicator
  • Dual element air filters
  • Single stage air cleaners

control panels

  • Cat connect (must choose one)
  • RTD module - may select one
  • Modbus monitoring of packages
  • First local annunicator
  • EMCP 4.3, EMCP 4.4
  • CAN2 network equipment
  • Remote custom annunciator
  • Locale discrete I / O package
  • Vandle proof panel door

cooling system

  • Optional radiator arrangements
  • Water level gauge
  • Coolant

control system

  • Generator temperature monitoring

exhaust system

  • Exhaust Y Adapters
  • Exhaust elbows
  • Mufflers
  • Flexible fittings
  • Exhaust flange and expanders

generators and attachments

  • Space heater control
  • Generator conversion
  • Space heater

instrumentation

  • Pyrometer and thermocouples

lube system

  • Oil level regulator
  • Prelube manual sump pump
  • Electric prelube sump pump
  • Lube oil

special tests / reports

  • PGS Test report @ 0.8 power factor
  • Generator test report
  • Standard generator TVA report
  • PGS Test report @ 0.8 power factor
  • Custom generator TVA report
  • Torsional vibration analysis
  • PGS Test report @ 1.0 power factor
  • Standard engine test charge
  • Generator test report
  • Standard engine test charge
  • PGS Test report @ 1.0 power factor
  • Generator fuel consumption test

general

  • Barring devices

crankcase system

  • Ventilation system
  • Protection systems

batteries and battery housing

  • 24 Volt battery set - Dry
  • Battery chargers - 10, 20 and 35 amp

power connection system

  • EMCP voltage and current sensing groups
  • Breaker power connections
  • Center post busbars

circuit breaker - lv packages

  • Right hand power connections
  • Electronically operated circuit breakers

mounting system

  • Low efficiency isolators
  • Spring type vibration isolators
  • Spring type vibration isolators
  • Low efficiency isolators puck

power connections

  • Low voltage - Package mounted circuit breakers
  • Low voltage - 1400 and 1600 Frame generators
  • Electrically operated circuit breakers
  • Low voltage - Power connection options

starting / charging system

  • Jacket water heater wiring groups
  • 35 Amp Battery charger
  • 20 Amp Battery charger
  • Jacket water heaters
  • 10 Amp Battery charger
  • Electric starting motors
  • Starter cover
  • Batteries, racks and cables

starting / charging systems

  • Electric starting motors
  • Starter cover
  • Jacket water heater

extended service coverage

  • Gold - 36,48, 60, 120 month coverage
  • Cat branded commercial power system
  • Silver - 36 ,48, 60, 120 month coverage
  • Platinum - 24, 36, 48, 60, 120 month coverage
Cat Switchgear

Cat Switchgear

Standby Rating:
1500/1400 kW
Prime Power Rating:
1360/1275 kW
Emissions/Fuel Strategy:
Low Fuel, Low Emissions
Voltage:
380 to 480 Volts