3516C (50 Hz) with Upgradeable Package
- new - Products
- 3516C (50 Hz) with Upgradeable Package
At a glance data:
Standby Rating:
2750 kVA
Prime Power Rating:
2500 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 11000 volts
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
Standby Rating:
2750 kVA
Prime Power Rating:
2500 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 11000 volts
Frequency:
50 Hz
Speed:
1500 rpm
Duty Cycle:
Standby, Mission Critical, Prime
Maximum Rating:
2750 kVA
Minimum Rating:
2500 kVA
Engine Specifications
Engine Model:
3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
Bore:
6.69in
Stroke:
8.46in
Displacement:
4765in
Compression Ratio:
14:01
Aspiration:
TA
Fuel System:
Electronic unit injection
Governor Type:
Adem™3
Generator Set Dimensions
Length - Maximum:
228.3in
Width - Maximum:
75.9in
Height - Maximum:
80.7in
Dry Weight - Genset (maximum):
32404lb
Standard Equipment
air inlet system
- Air cleaner
- Single element canister type with service indicator
control panel
- RPM
- Engine cycle crank
- Failure to start (overcrank)
- Warning/shutdown with common LED indication of shutdowns for:
- Speed adjust
- True RMS AC metering, 3-phase, +/-2% accuracy
- Accessory module data link
- Overcurrent (50/51)
- DC volts
- Controls:
- Generator phase sequence
- Low oil pressure
- 2 Programmable digital outputs
- Reverse power (kW) (32)
- Low coolant level
- Operating hours
- Frequency (Hz)
- kVAr-hr (total)
- kVA (per phase, average & percent)
- Lamp test
- Over/under frequency (81 o/u)
- 6 programmable digital inputs
- 2 Programmable relay outputs (Form C)
- 24 Volt DC operation
- Customer data link (Modbus RTU)
- EMCP 4 Genset controller
- Volts (L-L & L-N)
- High coolant temperature
- Alarm acknowledge
- Oil pressure (psi, kPa or bar)
- 4 Programmable relay outputs (Form A)
- Overspeed
- EMCP4.2B controller includes:
- Engine cool-down timer
- Panel lights
- kW (per phase, average & percent)
- Low coolant temperature
- Over/under voltage (27/59)
- Serial annunciator module data link
- Generator mounted - rear facing
- Communications:
- kVAr (per phase, average & percent)
- Digital indication for:
- Text alarm/event descriptions
- EMCP 4.2B
- Coolant temperature
- Emergency stop pushbutton
- Programmable protective relaying functions:
- kW-hr (total)
- Reverse reactive power (kVAr) (32RV)
- Amps (per phase & average)
- Environmental sealed front face
- Power factor (per phase & average)
exhaust
- Exhaust flange outlet
fuel
- Primary fuel filter with integral water separator
generator
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
power termination
- Busbar
starting/charging
- Heavy duty starting system
- Charging alternator
cooling system
- Fan and belt guards
- Coolant drain line with valve
- JWAC
- Caterpillar extended life coolant
- Coolant level sensors
- Radiator fan and fan drive
cooling
- Package mounted radiator
exhaust system
- Flanged faced outlet(s)
- Dry exhaust manifold
fuel system
- Flexible fuel lines - shipped loose
- Fuel priming pump
- Fuel cooler; not included with packages without radiator
- Secondary fuel filters
generators and attachments
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby).
- Busbar connections, top center mounted, top cable entry
- Random wound
- 6 Lead
- Winding temperature detectors
- IEC standard hole pattern
- Internal excitation (IE)
- 3 phase brushless, Salient pole
- Generator set packages include Caterpillar's digital voltage regulator (CDVR). CDVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
governing system
- ADEM III
literature
- Parts book
- Operation & Maintenance Manual
lube system
- Gear type lube oil pump
- Integral lube Oil cooler
- Fumes disposal
- Lubricating oil
- Oil filter, filler and dipstick
- Oil drain lines and valve
mounting system
- Rails - Engine/generator/radiator mounting
- Rubber anti-vibration mounts - shipped loose
starting / charging system
- 24 Volt electric starting motor
- Battery and battery rack w/cables
- Battery disconnect switch
general
- Right hand servicing
- Flywheel and flywheel housing-SAE No. 00
- Paint - Caterpillar yellow with high gloss black rails & radiator
- SAE standard rotation
Optional Equipment
air inlet system
- Remote air inlet adapters
- Dual element air cleaners
- Air inlet protection
- Heavy duty air cleaners
circuit breakers
- Cable entry options
- Control packaging for enclosures
- Trip units
- Load take off; IEC standard hole
- Busbar power connections
- Center posts busbars
- EMAX breakers
power termination
- Circuit breakers, IEC compliant
control panels
- Annunciator modules
- Generator temperature monitoring
- Auxiliary box
- Remote speed adjust
- Busbar connections
- Vandal proof panel door
- Voltage raise/lower switch
- EMCP 4.3, EMCP 4.4
- Local and remote monitoring
- Language options
- Customer interface options
- External box clips
- EMAX breaker connections
- Governors
cooling system
- Heat exchangers
- Water level switch gauges
- Radiator duct flanges
- Optional Serpentine radiators
european certifications
- EU Declaration of Conformity
exhaust system
- Through wall installation kit
- Muffler mounting kits
- Mufflers
- Flexible fittings
fuel system
- Fuel coolers
- Primary fuel filter
generators and attachments
- Generators
- 3 Phase, Random wound, Internal excitation (IE)
- Internal excitation (IE)
- 3 Phase, 380 / 400 / 415 / 3300 / 6600 / 10000 / 10500 / 11000 volt
- Number of leads: 6
- Pitch: 0.6667
instrumentation
- Pyrometers and thermocouples
- Thermocouples
lube system
- Oil level regulator
- Electric prelube pumps
- Manual prelube sump pumps
mounting system
- IBC vibration isolators
- Spring type vibration isolators
protection system
- Explosion relief valves
special tests / reports
- IBC seismic Certification
- CSA test and certification
- PGS Test report @ 1.0 power factor
- Neutral ground certificate
- PGS Test report @ 0.8 power factor
starting / charging system
- 10 and 20 Amp Battery chargers
- Charging alternators - 50 Amp
- Dual 24 volt electric starting motors
- ETHER starting aids
- 24 Volt battery set - Dry
- Jacket water heaters
general
- Engine barring group
Cat Switchgear
Standby Rating:
2750 kVA
Prime Power Rating:
2500 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 11000 volts
Similar Products
DE75AE0 (50 Hz) Generator Set
Standby Rating:
2750 kVA
Prime Power Rating:
2500 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 11000 volts
C9 Generator Set
Standby Rating:
2750 kVA
Prime Power Rating:
2500 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 11000 volts
DE165E0 (50 Hz) Generator Set
Standby Rating:
2750 kVA
Prime Power Rating:
2500 kVA
Emissions/Fuel Strategy:
Low Fuel Consumption
Voltage:
380 to 11000 volts