At a glance data:
Minimum Rating:
550 eKW (688 kVA)
Maximum Rating:
940 ekW (1175 kVA)
Frequency:
50 Hz or 60 Hz
Speed:
1500 rpm (50 hz) or 1800 rpm (60 hz)
Overview
C32 ACERT generator sets incorporate a separate circuit aftercooling system (SCAC) for all configurations. The primary advantage of the SCAC systsem is reduced aftercooler corrosion since no sea water circulates through the aftercooler. Many other improvements on these engines contribute to minimizing owning and operating costs. The IMO II and EU Stage IIIA compliant ratings are available with heat exchanger or keel cooled options. Heat exchanger configurations have an optional front mounted sea water pump.
Generator Set Specifications
Minimum Rating:
550 eKW (688 kVA)
Maximum Rating:
940 ekW (1175 kVA)
Frequency:
50 Hz or 60 Hz
Speed:
1500 rpm (50 hz) or 1800 rpm (60 hz)
Engine Specifications
Aspiration:
Twin Turbocharged-Aftercooled
Bore:
5.7in
Stroke:
6.4in
Displacement:
1959.0in³
Governor Type:
Electronic
Fuel System:
Diesel
Engine Model:
Vee 12, 4-Stroke-Cycle Diesel
Generator Set Specifications
Emissions/Fuel Strategy:
IMO II
Generator Set Dimensions
Length:
168.34in
Width:
65.79in
Height:
70.86in
Weight - Estimated:
15721.0lb
Generator Specifications
Excitation:
permanent magnet (PMG)
Pitch:
2/3
Number of Poles:
4
Number of Bearings:
2 roller bearings
Number of Leads:
6
Insulation:
Class H
Voltage Regulation:
± 0.5% (steady state)
Frame Size:
1423, 1467
IP Rating:
Drip Proof IP 23*
Alignment:
Closed-coupled adapter
Wave Form Deviation - Line to Line:
< 3.0%
Voltage Regulator:
Cat® Digital Voltage Regulator (CDVR)
Telephone Influence Factor (TIF):
< 50
Standard Equipment
air inlet system
- Separate circuit after-cooled (SCAC)
- Turbocharger, jacket water cooled
- Turbocharger inlet, 152 mm (6 in) OD straight connection
control system
- If an EMCP panel or MGCP option is not chosen as optional equipment, then start/stop controls must be provided by the customer
- Electronic diagnostics and fault logging
- Engine Protection Mode for extended ambient conditions
- Electronic fuel/air ratio control
cooling system
- Separate Circuit After-Cooling (SCAC) for Heat Exchanged (HEX) & Keel cooled engines
- Jacket Water (JW) and SCAC Heat Exchangers Shell & Tube for HEX cooled engines
- SCAC pump, gear driven
- Jacket water pump, gear driven
- Sea water pump, bronze impeller, gear driven, for HEX cooled engines only
- Jacket water HEX with Sea water pump Connections: 76.2 mm (3in) ID Standard
- 4 Bolt ANSI Flange Connection
- Jacket water HEX without Sea water pump Connection: 2.5" hose barb connection (inlet), 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange (outlet)
- Keel Connections: 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange Connection
- SCAC and JW shunt tanks for maintaining proper Pump inlet pressures
exhaust system
- Water-cooled exhaust manifold & turbocharger
- 4 Bolt 130 mm (5.12 in) diameter flanged outlet
flywheels & flywheel housings
- Flywheel Housing, SAE No. 0
- Flywheel, 18 inch, 136 teeth
- SAE standard rotation
fuel system
- Duplex Fuel Filters, Spin-on, RH service
- Fuel connections size: Supply JIC Deg -10 (7/8 - 14), Return JIC 37 Deg -8 (3/4 -16)
- Plate-type fuel cooler installed behind Aftercooler Shunt Tank
- Fuel transfer pump, gear driven
- Manual fuel priming pump
generators and generator attachments
- SR5 form wound
- 2 roller bearings
- Permanent magnet excitation
- 4 pole, 6 leads, Series Star connected
- Caterpillar's Digital Voltage Regulator (CDVR)
- Marine Class H insulation, Class F temperature rise
- Surface mounted platinum (PT100) 3-wire RTDs, 2 per phase on stator and one each on support bearings
- Anti-condensation space heaters (2 elements - 240 VAC, 1000 Watts
- IP23 Protection suitable for use with Fixed Water Based Local Application Fire Fighting Systems (FWBLAFFS)
- System IV insulation for harsh environment protection
lube system
- Simplex oil filters, RH service
- Deep sump oil pan
- RH service oil filler locations
- RH service dipstick
- Oil pump, gear driven
mounting system
- Formed C-channel rails, 300mm (11.81in) height
- Six shipped loose combined helical spring/rubber isolators for installation below package base
general
- Front damper guard
- Common electrical bonding point on HEX and KEEL cooled engines
Optional Equipment
alarm and protection
- Remote Panels
- MCS Controller
- Power analyzer module
- oil level, exhaust temperature, air starting pressure, heat exchanger pressure sensors
exhaust system
- Dry Elbows
- Flexible Fitting
- Flange
- Muffler
- Muffler Spark Arresting
- Rain Cap
air inlet system
- Air Inlet Cleaner
- Closed Crankcase Ventilation
- Air inlet adapter
charging system
- Battery Chargers, Charging Alternators
control system
- Load Sharing Attachment
fuel system
- Water Separator
lube system
- Duplex Oil Filters, Sump Pump
protection system
- Fuel and Oil Shielding
starting system
- Electric Starting Motors - Single 24 Volt
- Air Starting Motor
- Dual Starting Motors (Electric and Air)
- Air Start Accessories
- Starting Aids - JW Heaters
- Battery Sets - 24 Volt - Dry
Similar Products
Cat C32 ACERT Generator Set (IMO II)
Minimum Rating:
550 eKW (688 kVA)
Maximum Rating:
940 ekW (1175 kVA)
Frequency:
50 Hz or 60 Hz
Speed:
1500 rpm (50 hz) or 1800 rpm (60 hz)
C1.5 Marine Generator Set Engine
Minimum Rating:
550 eKW (688 kVA)
Maximum Rating:
940 ekW (1175 kVA)
Frequency:
50 Hz or 60 Hz
Speed:
1500 rpm (50 hz) or 1800 rpm (60 hz)
Cat C280-12 Marine Generator Set
Minimum Rating:
550 eKW (688 kVA)
Maximum Rating:
940 ekW (1175 kVA)
Frequency:
50 Hz or 60 Hz
Speed:
1500 rpm (50 hz) or 1800 rpm (60 hz)