Skip to content

Engine Paralleling and Integration Control (EPIC)

At a glance data:

Configuration:
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation:
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application:
LV and MV (208V-27kV)
ANSI Protective Devices:
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Overview

The Engine Paralleling and Integration Control (EPIC) product line provides standard paralleling controls in a remote cabinet separate from the engine generator set and separate from switchgear (breakers and bus).

Technical Summary

Configuration:
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation:
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application:
LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices:
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices:
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications:
UL / cUL 508A
Control Panel Enclosure:
NEMA 12
Operating Temperature:
0°C to 55°C
Storage Temperature:
-20°C to 60°C

Standard Equipment

instant auto selector switch

  • Allows user to return sysem to automatic in the event of a touchscreen failure

Optional Equipment

generator control panel (for 3-10 gensets)

  • With breaker position indications and circuit breaker control switch

utility control panel (for utility paralleling and control)

  • With utility close lockout switch, breaker position indications, and circuit breaker control switch

supplemental hardware 25 device

  • Provides additional discrete synchronization protection

data table interface

  • Accommodates interface with a building management system

generator demand priority control

  • An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity